FLOOR MIXING CONTROLLER

Preassembled regulation group (fixed-point or climatic electronic)

Composition
 
Components
1Flow bar for underfloor heating system with flow meters
2Flow bar for radiator heating system with regulation lockshields
3Return bar for radiator heating system set up for assembly of electro-thermal heads
4Return bar for underfloor heating system set up for assembly of electro-thermal heads
5Bar fixing brackets
6A Regulation valve with thermostatic head and immersion probe from 20 to 65 °C (not supplied)
6B Mixing valve with 3-point motorised valves or 0-10 Vdc (climatic version, not supplied as standard)
7Calibration valve and by-pass
8A Wilo Yonos Para Hu 15/6 wired circulator (with 3-core cable L=1000 mm)
8B Wilo Hu 15/6 wired circulator (with 3-core cable L=500 mm)
9Remote sensing probe pocket
10Control thermometers from 0 to 80 °C
11Box with safety thermostat for low-temperature circulation pump wiring (not supplied as standard)
12A Excess pressure valve (between 0.1 and 0.6 bar) one valve for the High Temperature zone
12B Excess pressure valve (between 0.1 and 0.6 bar) one valve for the Low Temperature zone (only in models with 3-speed Wilo Hu 15/6 circulator)
13Shut-off and balancing lockshield, for servicing
141/2” Automatic air vent
15Drain/fill valves with swivel connection and safety cap
16Circulator isolating valve, for servicing pump
17Valve Kit (optional)
18White plastified box (to be purchased separately)
19Electro-thermal heads (optional)
Characteristics
 
GENERAL CHARACTERISTICS
Max temperature on the primary circuit: 90 °C
Maximum operating pressure: 10 bar


COLLECTORS
Head thread G 1” F
Takeoffs M 24 x 19


REGULATION UNIT
Connections to the primary circuit G 1” M
(also G 1”1/4 M for without manifolds unit
Thermostatic head range of adjustment
(low temp.) 20 - 65 °C
Excess pressure valve range of
adjustment 0.1 - 0.6 bar
Thermometer scale 0 - 80 °C
Mixer valve pressure drops:
see Technical Annexes section


MIXER KIT MATERIALS
Brass UNI EN 12164 CW614N
PPA resin (35% glass reinforced)
EPDM 70 Sh o-ring gaskets
AISI 304 Stainless steel elements


COLLECTOR MATERIALS
Collectors obtained from drawn bar
Brass UNI EN 12168 CW614N
Collector seals in EPDM 70 Sh

CIRCULATION PUMP WILO YONOS PARA HU 15/6
Rotation speed: 800 - 4300 rpm.
Max static pressure: 6,2 m
Max delivery capacity: 2,6 m³/h
Power supply 1~230V, 50/60 Hz
Protection rating IPX 4D, for insulation F
Rated motor power: 37 W
Energy consumption from 1~230 V: 3 - 45 W
Current consumption at 1~230 V: 0,03 - 0,44 A
EEI<0,20


USABLE FLUIDS
Cooling and heating water.
Water and glycol: max 1:1
Max temperature water: 100 °C (at room temperature of 58 °C)
Max temperature water: 90 °C (at room temperature of 62 °C)
Max temperature water: 80 °C (at room temperature of 66 °C)
Max temperature water: 70 °C (at room temperature of 71 °C)


CONFORMITY
ErP directive
EN 61800-3
EN 61000-6-3 / EN 61000-6-4
EN 61000-6-2 / ENI 61000-6-1
2005/95/EC (Low voltage)

Performance diagrams in Technical attachments

THE RANGE
- Floor Mixing Controller A: High-temperature regulation and distribution unit (2- or 3-ways) and electronic circulator

- Floor Mixing Controller B: Low-temperature regulation and distribution unit (3- to 13-ways) and electronic circulator

- Floor Mixing Controller 2A + B: High-temperature 2-way + Low-temperature (3- to 13-ways) regulation and distribution unit and electronic circulator

- Floor Mixing Controller 3A + B: High-temperature 3-way + Low-temperature (3- to 12-ways) regulation and distribution unit and electronic circulator

- Floor Mixing Controller without manifolds: Mixing Low-temperature unit with electronic circulator, G 1” M or G 1”1/4 M threaded connections

___________________________________


- Floor Mixing Controller without manifolds: Mixing Low-temperature unit with 3-speed circulator, G 1” M or G 1”1/4 M threaded connections
(Articles exclusively for non-European markets)

Products
 
 
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
 
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
 
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
Preassembled adjustment unit (with fixed point or electronic climate) and distribution, fo...
 
Floor Mixing Controller without manifolds, with 3-speed Wilo HU 15/6 circulator.
G 1”...
Floor Mixing Controller without manifolds, with 3-speed Wilo HU 15/6 circulator.
G 1”...
 
Floor Mixing Controller without manifolds, with Wilo Yonos Para Hu 15/6 electronic circula...
Floor Mixing Controller without manifolds, with Wilo Yonos Para Hu 15/6 electronic circula...
 
Thermostatic head with immersion probe for fixed-point adjustment.
Adjustment range: 2...
Thermostatic head with immersion probe for fixed-point adjustment.
Adjustment range: 2...
 
Kit consisting of 2 Evolution valves with Blue/Red butterfly handles, with pipe union with...
Kit consisting of 2 Evolution valves with Blue/Red butterfly handles, with pipe union with...
 
Kit consisting of 2 Evolution ball angle valves with Blue/Red butterfly handles, wi...
Kit consisting of 2 Evolution ball angle valves with Blue/Red butterfly handles, wi...
 
Kit consisting of 2 Evolution straight Female-Female valves with Blue/Red butterfly, nicke...
Kit consisting of 2 Evolution straight Female-Female valves with Blue/Red butterfly, nicke...
 
Kit consisting of 2 Evolution angled Female-Female valves with Blue/Red butterfly handles,...
Kit consisting of 2 Evolution angled Female-Female valves with Blue/Red butterfly handles,...
 
Electrical box with safety thermostat for wiring of low temperature circulation pump.
Electrical box with safety thermostat for wiring of low temperature circulation pump.
 
Manifold cabinet for wall installation with telescopic body, door and frame in metal sheet...
Manifold cabinet for wall installation with telescopic body, door and frame in metal sheet...
 
Key lock for door of the Box System Plus metal box.
Key lock for door of the Box System Plus metal box.
 
 
 

NEWSLETTER

Launches Newsletter Keep in touch with events, offers and new FIV products!
 

TECHNICAL ASSISTANCE

Launches Assistenza Get support on our products